Evaluasi Penerapan Keselamatan Kebakaran Gedung Menggunakan Computerized Fire Safety Evaluation System (CFSES) di Fakultas Kedokteran Universitas Indonesia Tahun 2014

Dea Pisca Permaswhari; Pembimbing: Fatma Lestari; Penguji: Mila Tejamaya, Adrianus Pangaribuan (FKM UI, 2015)

Abstrak

Skripsi ini membahas evaluasi penerapan keselamatan kebakaran gedung dengan menggunakan perangkat lunak Computerized Fire Safety Evaluation System (CFSES) di Fakultas Kedokteran Universitas Indonesia yang berlokasi di Salemba, Jakarta Pusat. Evaluasi dilakukan berdasarkan kesesuaian 12 safety parameters dan persyaratan tambahan pada NFPA 101A: Alternate Approaches to Life Safety dengan standar NFPA 101: Life Safety Code. Disain studi penelitian adalah deskriptif dengan pendekatan semi kuantitatif. Sampel penelitian adalah Gedung Utama dan Gedung Departemen Kimia FKUI.
Hasil evaluasi Gedung Utama menunjukkan bahwa kontrol penyebaran api mendapatkan nilai -9 dari standar persyaratan minimum -4. Sistem jalan keluar mendapatkan nilai -12.5 dari standar 0. Sedangkan keselamatan kebakaran umum mendapatkan nilai -17 dari standar -4. Hasil evaluasi Gedung Departemen Kimia menunjukkan bahwa kontrol penyebaran api mendapatkan nilai -9,5 dari standar persyaratan minimum -4. Sistem jalan keluar mendapatkan nilai -5.5 dari standar 0. Sedangkan keselamatan kebakaran umum mendapatkan nilai -8 dari standar -4.
Hasil penelitian menyimpulkan bahwa penerapan keselamatan kebakaran di Gedung Fakultas kedokteran Universitas Indonesia belum memenuhi persyaratan keselamatan minimum pada NFPA 101: Life Safety Code.
Kata kunci : keselamatan kebakaran, gedung, CFSES, Fakultas Kedokteran Universitas Indonesia

This study discusses evaluation of the fire safety implementation of buildings using software Computerized Fire Safety Evaluation System (CFSES) at Faculty of Medicine, University of Indonesia, located in Salemba, Central Jakarta. The evaluation was done based on the suitability of 12 safety parameters and additional requirements in NFPA 101A: Alternate Approaches to Life Safety with standards NFPA 101: Life Safety Code. Design of this study is descriptive with a semi-quantitative approach. Samples are the Main Building and the Department of Chemistry Building, Faculty of Medicine.
Results of main building evaluation shows that the score of fire control is -9, score of egress is -12.5, and score of general fire safety is -17. Meanwhile, for chemistry building, the score for fire control is -9.5, score of egress is -5.5, and score of general fire safety is -8.
The study concluded that the fire safety implementation in the Faculty of Medicine University of Indonesia has not met the minimum safety requirements in NFPA 101: Life Safety Code.
Keywords: fire safety, building, CFSES, Faculty of Medicine University of Indonesia

Metadata

Jenis Koleksi : S1 - Skripsi
No. Panggil : S-8561
Pengarang :
Nama badan : Universitas Indonesia. Fakultas Kesehatan Masyarakat. Keselamatan dan Kesehatan Kerja
Program Studi/Peminatan : Keselamatan dan Kesehatan Kerja
Promotor/Pembimbing :
Ko-Promotor/Penguji :
Subjek :
Penerbitan : Depok : FKM UI, 2015
Kode Bahasa : ind
Tipe Carrier :
Deskripsi Fisik : xv, 131 hlm. il; 30 cm.
Departemen-Jurusan : Keselamatan dan Kesehatan Kerja
Kata Kunci : keselamatan kebakaran; gedung; CFSES; Fakultas Kedokteran Universitas Indonesia
Lembaga Pemilik : Pusinfokesmas FKM UI

File Digital: 1 

Shelf
 digital_2015-10_20402513-S58298-Dea Pisca Permaswhari.pdf ::
 
Catatan: Hanya file pdf yang dapat dibaca online
Menu Anggota Pusat Informasi Kesehatan Masyarakat
No. Panggil No. Barkod Ketersediaan Lokasi
S-8561 S-8561 TERSEDIA Lantai 5 / Annex
Ulasan:
Tidak ada ulasan pada koleksi ini: 112111

Sampul

cover

Lihat juga:

:: Pengguna : Pusat Informasi Kesehatan Masyarakat
Library Automation and Digital Archive