Ditemukan 40221 dokumen yang sesuai dengan query :: Simpan CSV
Kata kunci : Analisis Konsekuensi, Threat Zone, SPPBE, Dispersi Gas, kebakaran, ledakan, Jet Fire, BLEVE, Vapour Cloud Explosion
This study is about consequence analysis of gas dispersion, fire, andexplosion of LPG storage tank in SPPBE PT Aroma Jaya Sejati Sragen. Thisstudy is semi quantitave study using secondary data and field observation then analyze them with ALOHA software. The purpose of this study is to find out theconsequences impact range of gas dispersion, fire and explosion due to leakage ofLPG storage tank which divided into propane and butane gas.The result of this study is threat zone from gas dispersion, jet fire, BLEVE,and Vapour Cloud Explosion modelling. The result can show the heat radiationand explosion pressure and safe distance of SPPBE PT Aroma Jaya Sejati Sragen.
Keywords : Consequence Analysis, Threat Zone, SPPBE, Gas Dispersion, fire,explosion, Jet Fire, BLEVE, Vapour Cloud Explosion
This study is about consequence analysis of gas dispersion, fire, and explosionon LPG storage tank at SPPBE PT Adikarya Pramita Perdana, Depok. This study is aquantitative modeling with collecting secondary data and field observations thatanalyzed using ALOHA (Areal Location of Hazardous Atmosphere) software. Thepurpose of this study is to find out the consequences impact range of gas dispersion,fire and explosion due to leakage of LPG storage tank which divided into propaneand butane gas, also the description of fire safety system and emergency managementat SPPBE PT Adikarya Pramita Perdana.The results of this study is the range and consequences of modeling toxic gasdispersion due to leakage of LPG storage tank at SPPBE PT Adikarya PramitaPerdana, spreading range distance up to 401 meters. In jet fire model the range up to159 meters, while in BLEVE up to 1 kilometer, and VCE model up to 330 meters.The dangerous location or area due to this leakage at SPPBE PT Adikarya PramitaPerdana and the populations which is at risk reaches Sukamaju, Jatijajar, andCilodong. The installation of fire safety equipment at SPPBE PT Adikarya PramitaPerdana is already proper and meets the standard of PT Pertamina (Persero) and alsohas guidelines for emergency response management system for handling multiplecases of emergencies.Keywords: Consequence analysis, LPG, Storage Tank, SPPBE, ALOHA, Toxic gasdispersion, Fire, Jet fire, BLEVE, Explosion, Vapor cloud explosion, Firesafety, Emergency management
This study is about consequence analysis of gas dispersion, fire, and explosion of LPG spherical storage tank C – 20 – 01 – A at PT Pertamina (Persero) RU V Balikpapan. This study is a quantitative study using ALOHA software to analyze the primary and secondary data. This study aims to estimate the range and consequences of gas dispersion, fire, and explosion due to leakage at LPG spherical storage tank C – 20 – 01 – A which is divided to propane and butane.
Oil and gas companies are among the high-risk establishments explosion or fire (ILO, 1991). Explosions and fires can be classified into the category of great danger, because it may cause a big loss in a short time. The cause can be caused by many variables depending on the physical form of a material (solid, liquid or gas), physical properties (heat capacity, vapor pressure, burning heat, etc.) as well as its reactivity. This condition can actually be minimized by preventing and controlling risk, example analyzing the consequences of gas dispersion, fire and explosion caused by leakage of LPG storage tanks loaded with 30 tons in 2012 by using the descriptive quantitative research methods.
Hydrogen sulfide is a toxic gas that is contained on the installation of associated gas production of an oil and gas exploration industry. This thesis is adescriptive study with a semi-quantitative approach using secondary data from thecompany, literature and field observations. Then, these data are analyzed using thesoftware Areal Location of Hazardous Atmosphere (ALOHA). The purpose ofthis study was to determine the consequences that occur based on the range of gasdispersion, and population at risk to exposed of leakage scenarios that have beendesigned at the associated gas production installations.The results of this study found that the worst case scenario (uncontrolledrupture) in a 10 inches gas pipeline has the most extensive gas dispersion. Withinan hour, the farthest H2S gas dispersion with AEGL-1 0.51 ppm (60 min) reached3.6 km with a population at risk include people living in the surrounding area ofproduction station. Moreover, other results from this study were the level ofknowledge from population at risk about the dangers from gas leaks and gas leakssafety systems overview that available in PT.X.Keywords : Consequences analysis, Toxic gas dispersion, ALOHA, Associatedgas, Hidrogen Sulfida (H2S), Population at risk
Kata kunci : BREEZE Incident Analyst, tangki timbun, Premium, konsekuensi, dispersi gas, kebakaran,kolam api, BLEVE, ledakan.
Oil and gas industries normally use storage tanks containing flammable materials and hazardous to health, therefore the risk for the occurrence of gas dispersion, fire, andexplosion is very high when the failure happened storage tank. Modeling performed in thisstudy aimed to determine the consequences of the events of gas dispersion, fire and explosiondue to leakage in the Premium storage tank with a capacity of 5000 liters at PT Pertamina(Persero) Terminal BBM Panjang, Lampung which is an oil and gas industry. This research isa quantitative modeling. Modeling done using software BREEZE Incident Analyst at threetypes of hydrocarbons that become Premium components, namely hexane, heptane, andpentane.Results of this research are presented range and consequences of gas dispersion, fire,and explosion for the three zones based on the level of concern of each scenario. The rangeand consequences of this modeling will be analyzed by the system fire safety and emergencymanagement in PT Pertamina (Persero) Terminal BBM Lampung, Lampung.
Keywords:BREEZE Incident Analyst, storage tank, Premium, consequences, gas dispersion, fire, poolfire, BLEVE, explosion
ABSTRAK
Spherical tank yang berisi Butana merupakan subjek berpotensi hazard (kebocoran, kebakaran dan ledakan) yang dapat memberikan konsekuensi terhadap fasilitas dan manusia sebagai obyek penerima yang berada pada radius pajanan. Penelitian ini menggunakan pemodelan dengan input data primer dan sekunder yang diaplikasikan dalam perangkat lunak ALOHA, Area Locations of Hazardous Atmosphere. Hasil penelitian terhadap skenario kejadian kebocoran, kebakaran dan ledakan di fasilitas pengolahan minyak dan Gas PT Z mendapatkan nilai konsukeuensi zona bahaya sampai radius satu kilometer. Zona aman setelah radius satu kilometer.
ABSTRACT
Spherical tanks containing Butane is subject of potentially hazard (leak, fire and explosion) which can bring facility and human consequences as the recipient objects which are in the radius of exposure. This research uses input modeling with primary and secondary data which applied in the Area Locations of Hazardous Atmosphere (ALOHA) software. The study of the leak, fire and explosion incidence scenario at oil and gas processing facilities of PT Z scores shows threat zone to a radius of one kilometer. Safety zone distance after radius kilometer.